Line

Create Function

Lines can be either created from the standard type library (create_line) or with custom values (create_line_from_parameters).

Note

Lines for 3 phase load flow uses zero sequence parameters which can be provided through a custom standard type using pandapower.create_std_type() and pandapower.add_zero_impedance_parameters()

Zero sequence parameters (Added through std_type For Three phase load flow) :

-r0_ohm_per_km (float) - zero sequence line resistance in ohm per km

-x0_ohm_per_km (float) - zero sequence line reactance in ohm per km

-c0_nf_per_km (float) - zero sequence line capacitance in nano Farad per km

pandapower.create_line(net, from_bus, to_bus, length_km, std_type, name=None, index=None, geodata=None, df=1.0, parallel=1, in_service=True, max_loading_percent=nan, alpha=nan, temperature_degree_celsius=nan, **kwargs)

Creates a line element in net[“line”] The line parameters are defined through the standard type library.

INPUT:

net - The net within this line should be created

from_bus (int) - ID of the bus on one side which the line will be connected with

to_bus (int) - ID of the bus on the other side which the line will be connected with

length_km (float) - The line length in km

std_type (string) - Name of a standard linetype :

  • Pre-defined in standard_linetypes

or

  • Customized std_type made using create_std_type()

OPTIONAL:

name (string, None) - A custom name for this line

index (int, None) - Force a specified ID if it is available. If None, the index one higher than the highest already existing index is selected.

geodata (array, default None, shape= (,2L)) - The linegeodata of the line. The first row should be the coordinates of bus a and the last should be the coordinates of bus b. The points in the middle represent the bending points of the line

in_service (boolean, True) - True for in_service or False for out of service

df (float, 1) - derating factor: maximal current of line in relation to nominal current of line (from 0 to 1)

parallel (integer, 1) - number of parallel line systems

max_loading_percent (float) - maximum current loading (only needed for OPF)

alpha (float) - temperature coefficient of resistance: R(T) = R(T_0) * (1 + alpha * (T - T_0)))

temperature_degree_celsius (float) - line temperature for which line resistance is adjusted

tdpf (bool) - whether the line is considered in the TDPF calculation

wind_speed_m_per_s (float) - wind speed at the line in m/s (TDPF)

wind_angle_degree (float) - angle of attack between the wind direction and the line (TDPF)

conductor_outer_diameter_m (float) - outer diameter of the line conductor in m (TDPF)

air_temperature_degree_celsius (float) - ambient temperature in °C (TDPF)

reference_temperature_degree_celsius (float) - reference temperature in °C for which r_ohm_per_km for the line is specified (TDPF)

solar_radiation_w_per_sq_m (float) - solar radiation on horizontal plane in W/m² (TDPF)

solar_absorptivity (float) - Albedo factor for absorptivity of the lines (TDPF)

emissivity (float) - Albedo factor for emissivity of the lines (TDPF)

r_theta_kelvin_per_mw (float) - thermal resistance of the line (TDPF, only for simplified method)

mc_joule_per_m_k (float) - specific mass of the conductor multiplied by the specific thermal capacity of the material (TDPF, only for thermal inertia consideration with tdpf_delay_s parameter)

OUTPUT:

index (int) - The unique ID of the created line

EXAMPLE:

create_line(net, “line1”, from_bus = 0, to_bus = 1, length_km=0.1, std_type=”NAYY 4x50 SE”)

pandapower.create_line_from_parameters(net, from_bus, to_bus, length_km, r_ohm_per_km, x_ohm_per_km, c_nf_per_km, max_i_ka, name=None, index=None, type=None, geodata=None, in_service=True, df=1.0, parallel=1, g_us_per_km=0.0, max_loading_percent=nan, alpha=nan, temperature_degree_celsius=nan, r0_ohm_per_km=nan, x0_ohm_per_km=nan, c0_nf_per_km=nan, g0_us_per_km=0, endtemp_degree=nan, **kwargs)

Creates a line element in net[“line”] from line parameters.

INPUT:

net - The net within this line should be created

from_bus (int) - ID of the bus on one side which the line will be connected with

to_bus (int) - ID of the bus on the other side which the line will be connected with

length_km (float) - The line length in km

r_ohm_per_km (float) - line resistance in ohm per km

x_ohm_per_km (float) - line reactance in ohm per km

c_nf_per_km (float) - line capacitance (line-to-earth) in nano Farad per km

r0_ohm_per_km (float) - zero sequence line resistance in ohm per km

x0_ohm_per_km (float) - zero sequence line reactance in ohm per km

c0_nf_per_km (float) - zero sequence line capacitance in nano Farad per km

max_i_ka (float) - maximum thermal current in kilo Ampere

OPTIONAL:

name (string, None) - A custom name for this line

index (int, None) - Force a specified ID if it is available. If None, the index one higher than the highest already existing index is selected.

in_service (boolean, True) - True for in_service or False for out of service

type (str, None) - type of line (“ol” for overhead line or “cs” for cable system)

df (float, 1) - derating factor: maximal current of line in relation to nominal current of line (from 0 to 1)

g_us_per_km (float, 0) - dielectric conductance in micro Siemens per km

g0_us_per_km (float, 0) - zero sequence dielectric conductance in micro Siemens per km

parallel (integer, 1) - number of parallel line systems

geodata (array, default None, shape= (,2L)) - The linegeodata of the line. The first row should be the coordinates of bus a and the last should be the coordinates of bus b. The points in the middle represent the bending points of the line

max_loading_percent (float) - maximum current loading (only needed for OPF)

alpha (float) - temperature coefficient of resistance: R(T) = R(T_0) * (1 + alpha * (T - T_0)))

temperature_degree_celsius (float) - line temperature for which line resistance is adjusted

tdpf (bool) - whether the line is considered in the TDPF calculation

wind_speed_m_per_s (float) - wind speed at the line in m/s (TDPF)

wind_angle_degree (float) - angle of attack between the wind direction and the line (TDPF)

conductor_outer_diameter_m (float) - outer diameter of the line conductor in m (TDPF)

air_temperature_degree_celsius (float) - ambient temperature in °C (TDPF)

reference_temperature_degree_celsius (float) - reference temperature in °C for which r_ohm_per_km for the line is specified (TDPF)

solar_radiation_w_per_sq_m (float) - solar radiation on horizontal plane in W/m² (TDPF)

solar_absorptivity (float) - Albedo factor for absorptivity of the lines (TDPF)

emissivity (float) - Albedo factor for emissivity of the lines (TDPF)

r_theta_kelvin_per_mw (float) - thermal resistance of the line (TDPF, only for simplified method)

mc_joule_per_m_k (float) - specific mass of the conductor multiplied by the specific thermal capacity of the material (TDPF, only for thermal inertia consideration with tdpf_delay_s parameter)

OUTPUT:

index (int) - The unique ID of the created line

EXAMPLE:

create_line_from_parameters(net, “line1”, from_bus = 0, to_bus = 1, lenght_km=0.1, r_ohm_per_km = .01, x_ohm_per_km = 0.05, c_nf_per_km = 10, max_i_ka = 0.4)

Input Parameters

net.line

Parameter

Datatype

Value Range

Explanation

name

string

name of the line

std_type

string

standard type which can be used to easily define line parameters with the pandapower standard type library

from_bus*

integer

Index of bus where the line starts

to_bus*

integer

Index of bus where the line ends

length_km*

float

\(>\) 0

length of the line [km]

r_ohm_per_km*

float

\(\geq\) 0

resistance of the line [Ohm per km]

x_ohm_per_km*

float

\(\geq\) 0

inductance of the line [Ohm per km]

c_nf_per_km*

float

\(\geq\) 0

capacitance of the line (line-to-earth) [nano Farad per km]

r0_ohm_per_km****

float

\(\geq\) 0

zero sequence resistance of the line [Ohm per km]

x0_ohm_per_km****

float

\(\geq\) 0

zero sequence inductance of the line [Ohm per km]

c0_nf_per_km****

float

\(\geq\) 0

zero sequence capacitance of the line [nano Farad per km]

g_us_per_km*

float

\(\geq\) 0

dielectric conductance of the line [micro Siemens per km]

max_i_ka*

float

\(>\) 0

maximal thermal current [kilo Ampere]

parallel*

integer

\(\geq\) 1

number of parallel line systems

df*

float

0…1

derating factor (scaling) for max_i_ka

type

string

Naming conventions:
“ol” - overhead line
“cs” - underground cable system

type of line

max_loading_percent**

float

\(>\) 0

Maximum loading of the line

endtemp_degree***

float

\(>\) 0

Short-Circuit end temperature of the line

in_service*

boolean

True / False

specifies if the line is in service.

*necessary for executing a balanced power flow calculation
**optimal power flow parameter
***short-circuit calculation parameter
**** necessary for executing a three phase power flow / single phase short circuit .. note:

Defining a line with length zero leads to a division by zero in the power flow and is therefore not allowed. Lines with a very low impedance might lead to convergence problems in the power flow
for the same reason. If you want to directly connect two buses, please use the switch element instead of a line with a small impedance!

net.line_geodata

Parameter

Datatype

Explanation

coords

list

List of (x,y) tuples that mark the inflexion points of the line

Electric Model

Lines are modelled with the \(\pi\)-equivalent circuit:

alternate Text

Three phase line model

alternate Text

The elements in the equivalent circuit are calculated from the parameters in the net.line dataframe as:

\begin{align*} \underline{Z_{1 or 2}} &= (r\_ohm\_per\_km + j \cdot x\_ohm\_per\_km) \cdot \frac{length\_km}{parallel} \\ \underline{Y_{1 or 2}}&= (g\_us\_per\_km \cdot 1 \cdot 10^-6 + j \cdot 2 \pi f \cdot c\_nf\_per\_km \cdot 1 \cdot 10^-9) \cdot length\_km \cdot parallel\\ \underline{Z_{0}} &= (r0\_ohm\_per\_km + j \cdot x0\_ohm\_per\_km) \cdot \frac{length\_km}{parallel} \\ \underline{Y_{0}} &= (g\_us\_per\_km \cdot 1 \cdot 10^-6 + j \cdot 2 \pi f \cdot c0\_nf\_per\_km \cdot 1 \cdot 10^-9) \cdot length\_km \cdot parallel \end{align*}

The power system frequency \(f\) is defined when creating an empty network, the default value is \(f = 50 Hz\).

Note

For three phase load flow, three decoupled sequence networks ( zero , positive and negtive) are considered.

Positive and Negative sequence impedances are given by r_ohm_per_km, x_ohm_per_km, and c_nf_per_km

Zero sequence impedances are given by r0_ohm_per_km, x0_ohm_per_km, and c0_nf_per_km

The parameters are then transformed in the per unit system:

\begin{align*} Z_{N} &= \frac{V_{N}^2}{S_{N}} \\ \underline{z} &= \frac{\underline{Z}}{Z_{N}} \\ \underline{y} &= \underline{Y} \cdot Z_{N} \\ \end{align*}

Where the reference voltage \(V_{N}\) is the nominal voltage at the from bus and the rated apparent power \(S_{N}\) is defined system wide in the net object (see Unit Systems and Conventions).

Note

pandapower assumes that nominal voltage of from bus and to bus are equal, which means pandapower does not support lines that connect different voltage levels. If you want to connect different voltage levels, either use a transformer or an impedance element.

Result Parameters

net.res_line

Parameter

Datatype

Explanation

p_from_mw

float

active power flow into the line at “from” bus [MW]

q_from_mvar

float

reactive power flow into the line at “from” bus [MVar]

p_to_mw

float

active power flow into the line at “to” bus [MW]

q_to_mvar

float

reactive power flow into the line at “to” bus [MVar]

pl_mw

float

active power losses of the line [MW]

ql_mvar

float

reactive power consumption of the line [MVar]

i_from_ka

float

Current at from bus [kA]

i_to_ka

float

Current at to bus [kA]

i_ka

float

Maximum of i_from_ka and i_to_ka [kA]

vm_from_pu

float

voltage magnitude at from bus

vm_to_pu

float

voltage magnitude at to bus

va_from_degree

float

voltage angle at from bus [degrees]

va_to_degree

float

voltage angle at to bus [degrees]

loading_percent

float

line loading [%]

The power flow results in the net.res_line table are defined as:

\begin{align*} p\_from\_mw &= Re(\underline{v}_{from} \cdot \underline{i}^*_{from}) \\ q\_from\_mvar &= Im(\underline{v}_{from} \cdot \underline{i}^*_{from}) \\ p\_to\_mw &= Re(\underline{v}_{to} \cdot \underline{i}^*_{to}) \\ q\_to\_mvar &= Im(\underline{v}_{to} \cdot \underline{i}^*_{to}) \\ pl\_mw &= p\_from\_mw + p\_to\_mw \\ ql\_mvar &= q\_from\_mvar + q\_to\_mvar \\ i\_from\_ka &= i_{from} \\ i\_to\_ka &= i_{to} \\ i\_ka &= max(i_{from}, i_{to}) \\ loading\_percent &= \frac{i\_ka}{imax\_ka \cdot df \cdot parallel} \cdot 100 \end{align*}

net.res_line_3ph

Parameter

Datatype

Explanation

p_a_from_mw

float

active power flow into the line at from bus: Phase A [MW]

q_a_from_mvar

float

reactive power flow into the line at from bus : Phase A[MVar]

p_b_from_mw

float

active power flow into the line at from bus: Phase B [MW]

q_b_from_mvar

float

reactive power flow into the line at from bus : Phase B[MVar]

p_c_from_mw

float

active power flow into the line at from bus: Phase C [MW]

q_c_from_mvar

float

reactive power flow into the line at from bus : Phase C[MVar]

p_a_to_mw

float

active power flow into the line at to bus: Phase A [MW]

q_a_to_mvar

float

reactive power flow into the line at to bus : Phase A[MVar]

p_b_to_mw

float

active power flow into the line at to bus: Phase B [MW]

q_b_to_mvar

float

reactive power flow into the line at to bus : Phase B[MVar]

p_c_to_mw

float

active power flow into the line at to bus: Phase C [MW]

q_c_to_mvar

float

reactive power flow into the line at to bus : Phase C[MVar]

pl_a_mw

float

active power losses of the line: Phase A [MW]

ql_a_mvar

float

reactive power consumption of the line: Phase A [MVar]

pl_b_mw

float

active power losses of the line: Phase B [MW]

ql_b_mvar

float

reactive power consumption of the line: Phase B [MVar]

pl_c_mw

float

active power losses of the line: Phase C [MW]

ql_c_mvar

float

reactive power consumption of the line: Phase C [MVar]

i_a_from_ka

float

Current at from bus: Phase A [kA]

i_b_from_ka

float

Current at from bus: Phase B [kA]

i_c_from_ka

float

Current at from bus: Phase C [kA]

i_n_from_ka

float

Current at from bus: Neutral [kA]

i_a_to_ka

float

Current at to bus: Phase A [kA]

i_b_to_ka

float

Current at to bus: Phase B [kA]

i_c_to_ka

float

Current at to bus: Phase C [kA]

i_n_to_ka

float

Current at to bus: Neutral [kA]

i_ka

float

Maximum of i_from_ka and i_to_ka [kA]

loading_percent

float

line loading [%]

The power flow results in the net.res_line_3ph table are defined as:

\begin{align*} p\_from\_mw_{phase} &= Re(\underline{v_{phase}}_{from} \cdot \underline{i_{phase}}^*_{from}) \\ q\_from\_mvar_{phase} &= Im(\underline{v_{phase}}_{from} \cdot \underline{i_{phase}}^*_{from}) \\ p\_to\_mw_{phase} &= Re(\underline{v_{phase}}_{to} \cdot \underline{i_{phase}}^*_{to}) \\ q\_to\_mvar_{phase} &= Im(\underline{v_{phase}}_{to} \cdot \underline{i_{phase}}^*_{to}) \\ pl\_mw_{phase} &= p\_from\_mw_{phase} + p\_to\_mw_{phase} \\ ql\_mvar_{phase} &= q\_from\_mvar_{phase} + q\_to\_mvar_{phase} \\ i\_from\_ka_{phase} &= i_{from_{phase}} \\ i\_to\_ka_{phase} &= i_{to_{phase}} \\ i\_ka &= max(i_{from}, i_{to}) \\ i\_from\_ka_{neutral} &= |i_{from_{phaseA}}| + |i_{from_{phaseB}}| + |i_{from_{phaseC}}|\\ i\_to\_ka_{neutral} &= |i_{to_{phaseA}}| + |i_{to_{phaseB}}| + |i_{to_{phaseC}}| \\ loading\_percent &= \frac{i\_ka}{imax\_ka \cdot df \cdot parallel} \cdot 100 \end{align*}

net.res_line_est

The state estimation results are put into net.res_line_est with the same definition as in net.res_line.

Parameter

Datatype

Explanation

p_from_mw

float

active power flow into the line at “from” bus [MW]

q_from_mvar

float

reactive power flow into the line at “from” bus [MVar]

p_to_mw

float

active power flow into the line at “to” bus [MW]

q_to_mvar

float

reactive power flow into the line at “to” bus [MVar]

pl_mw

float

active power losses of the line [MW]

ql_mvar

float

reactive power consumption of the line [MVar]

i_from_ka

float

Current at from bus [kA]

i_to_ka

float

Current at to bus [kA]

i_ka

float

Maximum of i_from_ka and i_to_ka [kA]

vm_from_pu

float

voltage magnitude at from bus

vm_to_pu

float

voltage magnitude at to bus

va_from_degree

float

voltage angle at from bus [degrees]

va_to_degree

float

voltage angle at to bus [degrees]

loading_percent

float

line loading [%]

net.res_line_sc

The short-circuit (SC) results are put into net.res_line_sc with following definitions:

Parameter

Datatype

Explanation

ikss_ka

float

initial short-circuit current value [kA]

ikss_from_ka

float

magnitude of the initial SC current at “”from”” bus [kA]

ikss_from_degree

float

degree of the initial SC current at “”from”” bus [degrees]

ikss_to_ka

float

magnitude of the initial SC current at “”to”” bus [kA]

ikss_to_degree

float

degree of the initial SC current at “”to”” bus [degrees]

p_from_mw

float

active SC power flow into the line at “”from”” bus [MW]

q_from_mvar

float

reactive SC power flow into the line at “”from”” bus [MVar]

p_to_mw

float

active SC power flow into the line at “”to”” bus [MW]

q_to_mvar

float

reactive SC power flow into the line at “”to”” bus [MVar]

vm_from_pu

float

voltage magnitude at “”from”” bus [p.u.]

vm_to_pu

float

voltage magnitude at “”to”” bus [p.u.]

va_from_degree

float

voltage angle at “”from”” bus [degrees]

va_to_degree

float

voltage angle at “”to”” bus [degrees]

ip_ka

float

peak value of the short-circuit current [kA]

ith_ka

float

equivalent thermal short-circuit current [kA]