External Grid
Note
Power values of external grids are given in the generator system, therefore p_mw is negative if the external grid is absorbing power and positive if it is supplying/generating power.
See also
Create Function
- pandapower.create.create_ext_grid(net, bus, vm_pu=1.0, va_degree=0.0, name=None, in_service=True, s_sc_max_mva=nan, s_sc_min_mva=nan, rx_max=nan, rx_min=nan, max_p_mw=nan, min_p_mw=nan, max_q_mvar=nan, min_q_mvar=nan, index=None, r0x0_max=nan, x0x_max=nan, controllable=nan, slack_weight=1.0, **kwargs)
Creates an external grid connection.
External grids represent the higher level power grid connection and are modelled as the slack bus in the power flow calculation.
- INPUT:
net - pandapower network
bus (int) - bus where the slack is connected
- OPTIONAL:
vm_pu (float, default 1.0) - voltage at the slack node in per unit
va_degree (float, default 0.) - voltage angle at the slack node in degrees*
name (string, default None) - name of of the external grid
in_service (boolean) - True for in_service or False for out of service
s_sc_max_mva (float, NaN) - maximal short circuit apparent power to calculate internal impedance of ext_grid for short circuit calculations
s_sc_min_mva (float, NaN) - minimal short circuit apparent power to calculate internal impedance of ext_grid for short circuit calculations
rx_max (float, NaN) - maximal R/X-ratio to calculate internal impedance of ext_grid for short circuit calculations
rx_min (float, NaN) - minimal R/X-ratio to calculate internal impedance of ext_grid for short circuit calculations
max_p_mw (float, NaN) - Maximum active power injection. Only respected for OPF
min_p_mw (float, NaN) - Minimum active power injection. Only respected for OPF
max_q_mvar (float, NaN) - Maximum reactive power injection. Only respected for OPF
min_q_mvar (float, NaN) - Minimum reactive power injection. Only respected for OPF
r0x0_max (float, NaN) - maximal R/X-ratio to calculate Zero sequence internal impedance of ext_grid
x0x_max (float, NaN) - maximal X0/X-ratio to calculate Zero sequence internal impedance of ext_grid
slack_weight (float, default 1.0) - Contribution factor for distributed slack power flow calculation (active power balancing)
** only considered in loadflow if calculate_voltage_angles = True
- controllable (bool, NaN) - True: p_mw, q_mvar and vm_pu limits are enforced for the ext_grid in OPF. The voltage limits set in the ext_grid bus are enforced.
False: p_mw and vm_pu setpoints are enforced and limits are ignored. The vm_pu setpoint is enforced and limits of the bus table are ignored. defaults to False if “controllable” column exists in DataFrame
- EXAMPLE:
create_ext_grid(net, 1, voltage = 1.03)
For three phase load flow
create_ext_grid(net, 1, voltage=1.03, s_sc_max_mva=1000, rx_max=0.1, r0x0_max=0.1, x0x_max=1.0)
Input Parameters
net.ext_grid
Parameter |
Datatype |
Value Range |
Explanation |
name |
string |
name of the external grid |
|
bus* |
integer |
index of connected bus |
|
vm_pu* |
float |
\(>\) 0 |
voltage set point [p.u] |
va_degree* |
float |
angle set point [degree] |
|
max_p_mw** |
float |
Maximum active power |
|
min_p_mw** |
float |
Minimum active power |
|
max_q_mvar** |
float |
Maximum reactive power |
|
min_q_mvar** |
float |
Minimum reactive power |
|
s_sc_max_mva*** |
float |
\(>\) 0 |
maximum short circuit power provision [MVA] |
s_sc_min_mva*** |
float |
\(>\) 0 |
minimum short circuit power provision [MVA] |
rx_max*** |
float |
0…1 |
maxium R/X ratio of short-circuit impedance |
rx_min*** |
float |
0…1 |
minimum R/X ratio of short-circuit impedance |
r0x0_max**** |
float |
0…1 |
maximal R/X-ratio to calculate Zero sequence internal impedance of ext_grid |
x0x_max**** |
float |
0…1 |
maximal X0/X-ratio to calculate Zero sequence internal impedance of ext_grid |
in_service* |
boolean |
True / False |
specifies if the external grid is in service. |
*necessary for executing a power flow calculation
**optimal power flow parameter
***short-circuit calculation parameter
****Single phase short circuit/Three Phase load flow calculation parameters
Electric Model
** Balanced Load Flow** The external grid is modelled as a voltage source in the power flow calculation, which means the node the grid is connected to is treated as a slack node:
with:
** Unbalanced Load Flow / Single phase short ciruit **
The external grid is modelled as a voltage source for positive sequence model, which means the node the grid is connected to is treated as a slack node. For zero sequence and negative sequence external grid impedance is calculated:
Result Parameters
net.res_ext_grid
Parameter |
Datatype |
Explanation |
p_mw |
float |
active power supply at the external grid [MW] |
q_mvar |
float |
reactive power supply at the external grid [MVar] |
Active and reactive power feed-in / consumption at the slack node is a result of the power flow:
net.res_ext_grid_3ph
Parameter |
Datatype |
Explanation |
p_a_mw |
float |
active power supply at the external grid : Phase A [MW] |
q_a_mvar |
float |
reactive power supply at the external grid : Phase A [MVar] |
p_b_mw |
float |
active power supply at the external grid : Phase B [MW] |
q_b_mvar |
float |
reactive power supply at the external grid : Phase B [MVar] |
p_c_mw |
float |
active power supply at the external grid : Phase C [MW] |
q_c_mvar |
float |
reactive power supply at the external grid : Phase C [MVar] |
Active and reactive power feed-in / consumption at the slack node is a result of the power flow: