Ward¶
See also
Create Function¶
-
pandapower.
create_ward
(net, bus, ps_kw, qs_kvar, pz_kw, qz_kvar, name=None, in_service=True, index=None)¶ Creates a ward equivalent.
A ward equivalent is a combination of an impedance load and a PQ load.
- INPUT:
net (pandapowernet) - The pandapower net within the element should be created
bus (int) - bus of the ward equivalent
ps_kw (float) - active power of the PQ load
qs_kvar (float) - reactive power of the PQ load
pz_kw (float) - active power of the impedance load in kW at 1.pu voltage
qz_kvar (float) - reactive power of the impedance load in kVar at 1.pu voltage
- OUTPUT:
- ward id
Input Parameters¶
net.ward
Parameter | Datatype | Value Range | Explanation |
name | string | name of the ward equivalent | |
bus* | integer | index of connected bus | |
ps_kw* | float | constant active power demand [kW] | |
qs_kvar* | float | constant reactive power demand [kVar] | |
pz_kw* | float | constant impedance active power demand at 1.0 pu [kW] | |
qz_kvar* | float | constant impedance reactive power demand at 1.0 pu [kVar] | |
in_service* | boolean | True / False | specifies if the ward equivalent is in service. |
*necessary for executing a power flow calculation.
Electric Model¶

The ward equivalent is a combination of a constant apparent power consumption and a constant impedance load. The constant apparent power is given by:
The shunt admittance part of the ward equivalent is calculated as described here:
Result Parameters¶
net.res_ward
Parameter | Datatype | Explanation |
p_kw | float | active power demand of the ward equivalent [kW] |
q_kvar | float | reactive power demand of the ward equivalent [kVar] |
vm_pu | float | voltage at the ward bus [p.u] |