Storage¶
See also
Create Function¶
-
pandapower.
create_storage
(net, bus, p_kw, max_e_kwh, q_kvar=0, sn_kva=nan, soc_percent=nan, min_e_kwh=0.0, name=None, index=None, scaling=1., type=None, in_service=True, max_p_kw=nan, min_p_kw=nan, max_q_kvar=nan, min_q_kvar=nan, controllable = nan)¶ Adds a storage to the network.
In order to simulate a storage system it is possible to use sgens or loads to model the discharging or charging state. The power of a storage can be positive or negative, so the use of either a sgen or a load is (per definition of the elements) not correct. To overcome this issue, a storage element can be created.
As pandapower is not a time dependend simulation tool and there is no time domain parameter in default power flow calculations, the state of charge (SOC) is not updated during any power flow calculation. The implementation of energy content related parameters in the storage element allows to create customized, time dependend simulations by running several power flow calculations and updating variables manually.
- INPUT:
net - The net within this storage should be created
bus (int) - The bus id to which the storage is connected
p_kw (float) - The momentary real power of the storage (positive for charging, negative for discharging)
max_e_kwh (float) - The maximum energy content of the storage (maximum charge level)
- OPTIONAL:
q_kvar (float, default 0) - The reactive power of the storage
sn_kva (float, default None) - Nominal power of the storage
soc_percent (float, NaN) - The state of charge of the storage
min_e_kwh (float, 0) - The minimum energy content of the storage (minimum charge level)
name (string, default None) - The name for this storage
index (int, None) - Force a specified ID if it is available. If None, the index one higher than the highest already existing index is selected.
scaling (float, 1.) - An OPTIONAL scaling factor to be set customly
type (string, None) - type variable to classify the storage
in_service (boolean) - True for in_service or False for out of service
max_p_kw (float, NaN) - Maximum active power injection - necessary for a controllable storage in OPF
min_p_kw (float, NaN) - Minimum active power injection - necessary for a controllable storage in OPF
max_q_kvar (float, NaN) - Maximum reactive power injection - necessary for a controllable storage in OPF
min_q_kvar (float, NaN) - Minimum reactive power injection - necessary for a controllable storage in OPF
controllable (bool, NaN) - Whether this storage is controllable by the optimal powerflow
- OUTPUT:
- index (int) - The unique ID of the created storage
- EXAMPLE:
- create_storage(net, 1, p_kw = -30, max_e_kwh = 60, soc_percent = 1.0, min_e_kwh = 5)
Input Parameters¶
net.storage
Parameter | Datatype | Value Range | Explanation |
name | string | name of the storage unit | |
bus* | integer | index of connected bus | |
p_kw* | float | \(\leq\) 0 | Momentary real power of the storage (positive for charging, negative for discharging) |
q_kvar* | float | Reactive power of the storage [kVar] | |
sn_kva | float | \(>\) 0 | Nominal power ot the storage [kVA] |
scaling* | float | \(\geq\) 0 | scaling factor for the active and reactive power |
soc_percent | float | 0 \(\leq\) soc_percent \(\leq\) 100 | The state of charge of the storage |
max_e_kwh | float | The maximum energy content of the storage (maximum charge level) | |
min_e_kwh | float | The minimum energy content of the storage (minimum charge level) | |
max_p_kw** | float | Maximum active power | |
min_p_kw** | float | Minimum active power | |
max_q_kvar** | float | Maximum reactive power | |
min_q_kvar** | float | Minimum reactive power | |
controllable** | bool | States if sgen is controllable or not, sgen will not be used as a flexibilty if it is not controllable | |
in_service* | boolean | True / False | specifies if the generator is in service. |
*necessary for executing a power flow calculation
**optimal power flow parameter
Electric Model¶
Storages are modelled as PQ-buses in the power flow calculation:

The PQ-Values are calculated from the parameter table values as:
Note
Since all power values are given in the consumer system, negative power models charging and positive activee power models discharging.
Note
The apparent power value sn_kva, state of charge soc and storage capacity max_e_kwh are provided as additional information for usage in controller or other applications based on panadapower. It is not considered in the power flow!
Result Parameters¶
net.res_storage
Parameter | Datatype | Explanation |
p_kw | float | resulting active power after scaling [kW] |
q_kvar | float | resulting reactive power after scaling [kVar] |
The power values in the net.res_storage table are equivalent to \(P_{storage}\) and \(Q_{storage}\).