Static Generator¶
Note
Static generators should always have a positive p_mw value, since all power values are given in the generator convention. If you want to model constant power consumption, it is recommended to use a load element instead of a static generator with negative active power value. If you want to model a voltage controlled generator, use the generator element.
See also
Create Function¶
-
pandapower.
create_sgen
(net, bus, p_mw, q_mvar=0, sn_mva=nan, name=None, index=None, scaling=1.0, type='wye', in_service=True, max_p_mw=nan, min_p_mw=nan, max_q_mvar=nan, min_q_mvar=nan, controllable=nan, k=nan, rx=nan, current_source=True)¶ Adds one static generator in table net[“sgen”].
Static generators are modelled as positive and constant PQ power. This element is used to model generators with a constant active and reactive power feed-in. If you want to model a voltage controlled generator, use the generator element instead.
gen, sgen and ext_grid in the grid are modelled in the generator system! If you want to model the generation of power, you have to assign a positive active power to the generator. Please pay attention to the correct signing of the reactive power as well (positive for injection and negative for consumption).
- INPUT:
net - The net within this static generator should be created
bus (int) - The bus id to which the static generator is connected
p_mw (float) - The active power of the static generator (positive for generation!)
OPTIONAL:
q_mvar (float, 0) - The reactive power of the sgen
sn_mva (float, None) - Nominal power of the sgen
name (string, None) - The name for this sgen
index (int, None) - Force a specified ID if it is available. If None, the index one higher than the highest already existing index is selected.
scaling (float, 1.) - An OPTIONAL scaling factor to be set customly
type (string, None) - Three phase Connection type of the static generator: wye/delta
in_service (boolean) - True for in_service or False for out of service
max_p_mw (float, NaN) - Maximum active power injection - necessary for controllable sgens in OPF
min_p_mw (float, NaN) - Minimum active power injection - necessary for controllable sgens in OPF
max_q_mvar (float, NaN) - Maximum reactive power injection - necessary for controllable sgens in OPF
min_q_mvar (float, NaN) - Minimum reactive power injection - necessary for controllable sgens in OPF
controllable (bool, NaN) - Whether this generator is controllable by the optimal powerflow
Defaults to False if “controllable” column exists in DataFrame
k (float, NaN) - Ratio of nominal current to short circuit current
rx (float, NaN) - R/X ratio for short circuit impedance. Only relevant if type is specified as motor so that sgen is treated as asynchronous motor
current_source (bool, True) - Model this sgen as a current source during short- circuit calculations; useful in some cases, for example the simulation of full- size converters per IEC 60909-0:2016.
- OUTPUT:
index (int) - The unique ID of the created sgen
- EXAMPLE:
create_sgen(net, 1, p_mw = -120)
-
pandapower.
create_sgen_from_cosphi
(net, bus, sn_mva, cos_phi, mode, **kwargs)¶ Creates an sgen element from rated power and power factor cos(phi).
- INPUT:
net - The net within this static generator should be created
bus (int) - The bus id to which the static generator is connected
sn_mva (float) - rated power of the generator
cos_phi (float) - power factor cos_phi
mode (str) - “ind” for inductive or “cap” for capacitive behaviour
- OUTPUT:
index (int) - The unique ID of the created sgen
gen, sgen, and ext_grid are modelled in the generator point of view. Active power will therefore be postive por generation, and reactive power will be negative for consumption behaviour and positive for generation behaviour.
Input Parameters¶
net.sgen
Parameter |
Datatype |
Value Range |
Explanation |
name |
string |
name of the static generator |
|
type |
string |
naming conventions:
“PV” - photovoltaic system
“WP” - wind power system
“CHP” - combined heating and power system
|
type of generator |
bus* |
integer |
index of connected bus |
|
p_mw* |
float |
\(\leq\) 0 |
active power of the static generator [MW] |
q_mvar* |
float |
reactive power of the static generator [MVar] |
|
sn_mva |
float |
\(>\) 0 |
rated power ot the static generator [MVA] |
scaling* |
float |
\(\geq\) 0 |
scaling factor for the active and reactive power |
max_p_mw** |
float |
Maximum active power [MW] |
|
min_p_mw** |
float |
Minimum active power [MW] |
|
max_q_mvar** |
float |
Maximum reactive power [MVar] |
|
min_q_mvar** |
float |
Minimum reactive power [MVar] |
|
controllable** |
bool |
States if sgen is controllable or not, sgen will not be used as a flexibilty if it is not controllable |
|
k*** |
float |
\(\geq\) 0 |
Ratio of nominal current to short circuit current |
rx*** |
float |
\(\geq\) 0 |
R/X ratio for short circuit impedance. Only relevant if type is specified as motor so that sgen is treated as asynchronous motor |
in_service* |
boolean |
True / False |
specifies if the generator is in service. |
*necessary for executing a power flow calculation
**optimal power flow parameter
Electric Model¶
Static Generators are modelled as PQ-buses in the power flow calculation:
The PQ-Values are calculated from the parameter table values as:
Note
The apparent power value sn_mva is provided as additional information for usage in controller or other applications based on panadapower. It is not considered in the power flow!
Result Parameters¶
net.res_sgen
Parameter |
Datatype |
Explanation |
p_mw |
float |
resulting active power demand after scaling [MW] |
q_mvar |
float |
resulting reactive power demand after scaling [MVar] |
The power values in the net.res_sgen table are equivalent to \(P_{sgen}\) and \(Q_{sgen}\).