Current Source Elements

Full converter elements, such as PV plants or wind parks, are modeled as current sources:

../_images/bus_current.png

All static generator elements are assumed to be full converter elements except if the type is specified as “motor”, in which case they are treated as asynchronous machines.

The inductive short circuit current is calculated from the parameters given in the sgen table as:

\[\underline{I}_k = -j \cdot \frac{k \cdot s\_n\_kva}{\sqrt{3} \cdot vn\_kv}\]

where \(s\_n\_kva\) is the rated power of the generator and \(k\) is the ratio of nominal to short circuit current. \(vn\_kv\) is the rated voltage of the bus the generator is connected to.